Home › Projects › Emergency backup lighting, Edinburgh

Project Case Study · Commercial Electrical

Emergency Backup Lighting Edinburgh Freight Terminal

An office at a freight terminal in Edinburgh had a newer 2x4 LED troffer with no battery backup, so the room would go dark in a power outage. The facility wanted that fixture to keep lighting the room when the power drops.

Since 2005BBB A+ Accredited4.9★ Google ratingLicensed General Contractor · $2M General LiabilityMon–Fri 8–6 · Sat 9–2

Short version: we installed a UL 924 emergency LED driver with a 90-minute battery inside the existing fixture, wired it to an unswitched hot so the battery stays charged, added the test button and charge indicator, and tested the changeover.

Before: open ceiling grid above the office. After: the LED troffer lit, with the emergency test indicator in the ceiling tile.
Before and after. Ceiling opened up, then the fixture back in with its emergency indicator.

The Problem

The office fixture had been replaced with a modern LED troffer, but the replacement had no emergency battery. That left a working office without light during an outage.

What We Did

  1. Site visit: opened the ceiling, read the fixture's label and LED driver specs, and confirmed an unswitched hot was available.
  2. Specified the driver: a UL 924 emergency LED driver with 90-minute backup, matched to the fixture.
  3. Installed and wired it in flexible conduit, mounted to the fixture housing.
  4. Added the test switch and charge indicator in the ceiling so staff can check it.
  5. Tested the changeover and closed up the ceiling grid.
Project at a glance
Property typeFreight terminal office
CityEdinburgh, Indiana
TradeCommercial electrical, emergency lighting
VisitsSite visit, then install

Have Something Like This at Your Property?

Call or text 317-893-3717, or use the estimate form on this page. Send a few photos and we will tell you what it needs and give you a written estimate before any work starts. More on Electrical repair or Commercial maintenance.

Common Questions

Can you add battery backup to an existing LED light?

In many cases, yes. An emergency LED driver mounts inside or next to the fixture and takes over when power fails. It has to be matched to the fixture's LED driver and needs an unswitched hot to keep the battery charged.

What does UL 924 mean?

UL 924 is the safety standard for emergency lighting equipment. A UL 924 listed driver is built and tested to provide emergency illumination for a set time, here 90 minutes, when normal power is lost.

Do you do full electrical service work?

We handle minor electrical repairs and like-for-like fixture work on existing circuits, like this job. Panel work, new circuits and service upgrades are outside our scope. See electrical repair.